Digite | Faixa de temperatura (°C) | Classe de Tolerância (°C) | ||||
Continuous | Curto prazo | Um | Dois | |||
Baixa | Alta | Baixa | Alta | |||
K | 0 | +1100 | -180 | +1300 |
-40 - 375: ±1, 5
375 - 1000: ±0, 004× T |
-40 - 333: ±2, 5
333 - 1200: ± 0, 0075 × T |
J | 0 | +750 | -180 | +800 |
-40 - 375: ±1, 5
375 - 750: ±0, 004× T |
-40 - 333: ±2, 5
333 - 750: ± 0, 0075 × T |
N | 0 | +1100 | -270 | +1300 |
-40 - 375: ±1, 5
375 - 1000: ±0, 004× T |
-40 - 333: ±2, 5
333 - 1200: ± 0, 0075 × T |
R | 0 | +1600 | -50 | +1700 |
0 - 1100: ±1, 0
1100 - 1600: ±0, 003×( T -767) |
0 - 600: ±1, 5
600 - 1600: ± 0, 0025 × T |
S | 0 | +1600 | -50 | +1750 |
0 - 1100: ±1, 0
1100 - 1600: ±0, 003×( T -767) |
0 - 600: ±1, 5
600 - 1600: ± 0, 0025 × T |
B | +200 | +1700 | 0 | +1820 | Não disponível | 600 - 1700: ± 0, 0025 × T |
T | -185 | +300 | -250 | +400 |
-40 - 125: ±0, 5
125 - 350: ±0, 004× T |
-40 - 133: ±1, 0
133 - 350: ± 0, 0075 × T |
E | 0 | +800 | -40 | +900 |
-40 - 375: ±1, 5
375 - 800: ±0, 004× T |
-40 - 333: ±2, 5
333 - 900: ± 0, 0075 × T |
Chromel
/AuFe |
-272 | +300 | N/A | N/A |
Reprodutibilidade 0, 2% da tensão.
Cada sensor necessita de calibração individual. |
• Degelo
• Banhos de Galvanoplastia
• Processamento Industrial
• Equipamento Médico
• Controle de rastreamento do Tubo
• Tratamento térmico Industrial
• Equipamentos de embalagem
• A medição da temperatura de líquido
• Controle de temperatura do frigorífico
• Controle de temperatura do forno